BA1R

KEY FEATURES

  • Multi-function or mono-function
  • Multi-range (7 ranges)
  • Multi-voltage 12 →240 V AC/DC
  • LED status indicator (relay version)
  • Possibility of external load connection in parallel to the control input
  • 3-wire PNP sensor compatible
FunctionsTimingOutputNominal ratingConnectionsSupply voltageCode
A - At0,5 s →240 h1 changeover relay16 AScrew terminals12 →240 V ∿/⎓BA1R16MV1

Specifications


Output relay 1 CO (SPDT) (ChangeOver -Simple Pole Double Throw-)
Voltage breaking capacity 250 V∿/ 16 A resistive / 250 V⎓ / 0,3 A resistive
Maximum breaking current NO / NC : 16 A 250 V∿ / 16 A 30 V⎓ @ 25 °C NO / NC : 8 A 250 V∿ / 8 A 30 V⎓ @ 60 °C
Minimum breaking current 10 mA / 5 V⎓
Breaking capacity 4000 VA / 90 W @ 25 °C
Electrical life (number of operations) 30 x 103 cycles (NO) @ 250 V∿/ 16 A resistive
Maximum rate (at full load) 360 cycles / hour
Mechanical life (operations) 30 x 106 cycles
Impulse voltage CEI/EN 60664-1 CEI/ EN 61812-1 5 kV (1,2 / 50 μs)
Dielectric strength between coil / contacts IEC 60664-1 : 5 kV / 1 min / 1 mA / 50 Hz
Dielectric strength between connexions 1 kV / 1 min / 1 mA / 50 Hz

Timing ranges (7 ranges) 0.5 →10 s, 0.05 →1 min, 0.5 →10 min, 0.05 →1 h, 0.5 →10 h, 0.05 →1 day, 0.5 →10 days
Minimum pulse duration typically (relay version) IEC 1812-1 30 ms 100 ms with load
Maximum reset time by de-energisation typically (relay version) IEC 1812-1 120 ms
Repeatability IEC 1812-1 ≤ ± 0,5 %
Repetition accuracy with constant parameters IEC 1812-1 ≤ ± 10 %
Drift Temperature ≤ ± 0.05 % / °C
Voltage-dependent drift ≤ ± 0.2 % / V

Multi-voltage power supply 12→240 V∿/⎓
Operating range 15 %, +10 %
Operating frequency (Hz) 50 / 60 Hz ± 5 %
Galvanic isolation No
Max. absorbed power Approx. 3 VA (V∿) 1.5 W (V⎓)
Immunity from micro power cuts 10 ms

Insulation voltage, IEC 60664-1 300 V
Installation category (acc. to IEC/EN 60664-1) Overvoltage category III ; pollution degree 2
Impulse voltage CEI/EN 60664-1 4 kV (1,2 / 50 μs)
Clearance / creepage distance IEC 60664-1 3 mm / 3.2 mm
Breakdown voltage EN-61812-1 2,5 kV / 1 min / 1 mA / 50 Hz
Insulation resistance NFC 93 050 > 500 MΩ / 250 V⎓ / 1min
Status indication Un : green LED blinks when count, continuous ON when supplied R : yellow LED continuous ON when the relay is ON
Casing DIN 43880 17,5 mm
Fixing : Symmetrical DIN rail EN 50022 35 mm
Mounting position All positions
Housing material Enclosure plastic type UL94 - V0
Protection (IEC/EN 60529) Housing : IP40 / Terminal block : IP20
Terminal capacity Single-wire without ferrule IEC 60947-1 1 x 0.5 →3.3 mm2 (AWG 20 →AWG 12) 2 x 0.5 →1.5 mm2 (AWG 20 →AWG 16)
Max. tightening torque (Nm) IEC 60947-1 0,5 N.m / 4,4 lbf.in
Operating temperature range (°C) IEC 60068-2 -20 °C →+60 °C
Storage temperature range (°C) IEC 60068-2 -40 °C →+70 °C
Relative humidity no condensation acc. to IEC/EN 60068-2-30 93 % without condensation
Vibration resistance according to IEC/EN 60068-2-6 ± 0.15 mm de 10 Hz →60 Hz 2G de 60 Hz →150 Hz
Impact resistance IEC 60068-2-27 15gn - 11ms ; 3 x 6 axis (output OFF) 5gn - 11ms ; 3 x 6 axis (Output ON)
Drop to concrete floor IEC 60068-2-32 High : 0.75m
Weight : casing 17,5 mm 70 g 80g with packaging
Directives 2014/30/EU : EMC 2014/35/EU : low voltage
Certifications CE - cULus Listed Industrial Control Equipment - CCC
Conformity to standards CEI 60664-1 : Insulation coordination for equipment within low-voltage systems CEI 61812-1/ Specified time relays for industrial use UL 60947-4-1/ Industrial Control Equipment (NRNT- Industrial Control Switches)
Conformity with environmental directives 2015/863/UE : RoHS 1907/2006 : Reach 2012/19/UE : WEEE
Electromagnetic compatibility IEC 61000-6-2, IEC 61000-6-3, IEC 61000-6-4 Immunity for industrial environment Emission residential environment Emission industrial environment
Electromagnetic compatibility - Immunity to electrostatic discharges acc to IEC/EN 61000-4-2 Level III Air ± 8 KV / Contact ± 6 KV
Immunity to radiated, radio-frequency, electromagnetic field acc. IEC/EN 61000-4-3 Level III 10 V/m (80 M Hz to 1 G Hz) 80 % AM (1 k Hz) 3 V/m (1,4 →2 G Hz) 80 % AM (1K Hz) 1V/m (2 →2.7 G Hz) 80 % AM (1K Hz)
Immunity to rapid transient bursts acc. to IEC/EN 61000-4-4 Level III direct ± 2 kV (power supply) / capacitive coupling clamp ± 1 KV (command input and outputs)
Immunity to shock waves on power supply acc. to IEC/EN 61000-4-5 Level III line-to-earth ± 2 kV / line-to-line ± 1kV
Immunity to radio frequency in common mode acc. to IEC/EN 61000-4-6 Level III 10 Vrms (0,15 →80 M Hz) 80 % AM (1 k Hz)
Immunity to voltage dips and breaks acc. to IEC/EN 61000-4-11 Industrial Class II : 0 % residual voltage during 1cycle a.c. power ports 70 % residual voltage during 25/30 cycles a.c. power ports 0 % residual voltage, 250/300 cycles a.c. power ports Residential : 0 % residual voltage during 10 cycle a.c.power ports 40 % residual voltage during 10 cycles a.c. power ports 70 % residual voltage during 10 cycles a.c. power ports 0 % residual voltage, 250/300 cycles a.c. power ports
Mains-borne and radiated emissions acc. to EN 55022 (CISPR22), EN55011 (CISPR11) EN 55022 / CISPR22 Class B (IT equipment) EN 55011 / CISPR11 Class B, Group 1 (Medical equipment)

Technical sketches

BA1R

BA1R

1 changeover relay output

1 changeover relay output

Function At

Function At
Legend
Delay on energisation 1 relay-

Function A

Function A
Legend
Timing on energisation with memory-
SYR-LINE

Share
Share
sed dolor. ipsum risus. Praesent accumsan ut