MUS2

KEY FEATURES

  • Multi-function or mono-function
  • Multi-range
  • Multi-voltage
  • Screw or spring terminals
  • LED status indicator (relay version)
  • Possibility of external load connection in parallel to the control input
  • 3-wire PNP sensor compatible
FunctionsTimingOutputNominal ratingConnectionsSupply voltageCode
A - Ac - At - B - Bw - C - D - Di - H - Ht0,1 s →100 hSolid state0,7 AScrew terminals24 →240 V ∿88827004

Specifications


Timing ranges (7 ranges) 1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
Repetition accuracy with constant parameters ± 0.5 % (IEC/EN 61812-1)
Drift Temperature ± 0,05 % / °C
Drift Voltage ± 0,2 % / V
Display accuracy according to IEC/EN 61812-1 ± 10 % / 25 °C
Immunity from micro power cuts : typical < 10 ms

Multi-voltage power supply Depending on version
Frequency (Hz) 50 / 60
Operating factor 100 %

Rated power 2000 VA/80 W
Maximum breaking current 8 A∿ 250 V∿ resistive 8 A⎓ 30 V⎓ resistive
Minimum breaking current 10 mA / 5 V⎓
Voltage breaking capacity 250 V∿ / 8 A∿ resistive 250 V⎓ / 0,3 A resistive
Electrical life (operations) 105 8 A 250 V∿ resistive
Mechanical life (operations) 10 x 106
Breakdown voltage acc. to IEC/EN 61812-1 2,5 kV / 1 min / 1 mA / 50 Hz
Impulse voltage acc. to IEC/EN 60664-1, IEC/EN 61812-1 5 kV wave 1.2 / 50 μs

Conformity to standards IEC/EN 61812-1 IEC/EN 61000-6-1 IEC/EN 61000-6-2 IEC/EN 61000-6-3 IEC/EN 61000-6-4
Certifications CE, UL, cUL, CSA, GL
Temperature limits use (°C) -20 →+60
Temperature limits stored (°C) -30 →+60
Installation category (acc. to IEC/EN 60664-1) Voltage surge category III
Creepage distance and clearance acc. to IEC/EN 60664-1 4 kV / 3 mm
Protection (IEC/EN 60529) IP20
IP40
Degree of protection acc. to IEC/EN 60529 Front face IP50
Vibration resistance acc. to IEC/EN 60068-2-6 20 m/s2 10 Hz →150 Hz
Relative humidity no condensation acc. to IEC/EN 60068-2-30 93 % non-condensing
Electromagnetic compatibility - Immunity to electrostatic discharges acc to IEC/EN 61000-4-2 Level III (Air 8 kV / Contact 6 kV)
Immunity to radiated, radio-frequency, electromagnetic field acc. IEC/EN 61000-4-3 Level I (1 V/m : 2,0 G Hz →2,7 G Hz) Level II (3 V/m : 1,4 G Hz →2,0 G Hz) Level III (10 V/m : 80 M Hz →1 G Hz)
Immunity to rapid transient bursts acc. to IEC/EN 61000-4-4 Level III (direct 2 kV / Capacitive coupling clamp 1 kV)
Immunity to shock waves on power supply acc. to IEC/EN 61000-4-5 Level III (2 kV / common mode 2 kV/residual current mode 1 kV)
Immunity to radio frequency in common mode acc. to IEC/EN 61000-4-6 Level III (10V rms : 0.15 M Hz to 80 M Hz)
Immunity to voltage dips and breaks acc. to IEC/EN 61000-4-11 0 % residual voltage, 1 cycle 70 % residual voltage, 25/30 cycles
Mains-borne and radiated emissions acc. to EN 55022 (CISPR22), EN55011 (CISPR11) Class B
Fixing : Symmetrical DIN rail 35 mm
Terminal capacity Single-wire without ferrule 1 x 0,5 →3,3 mm2 (AWG 20 →AWG 12) 2 x 0,5 →2,5 mm2 (AWG 20 →AWG 14)
Terminal capacity Multi-wire with ferrule 1 x 0,5 →2,5 mm2 (AWG 20 →AWG 14) 2 x 0,5 →1,5 mm2 (AWG 20 →AWG 16)
Housing material Self-extinguishing
Shock test IEC/EN 60068-2-27 15 g - 11 ms
Short interruption on power line acc to IEC/EN 61000-4-11 0 % residual voltage, 250/300 cycles

Breaking capacity 0,7 A ∿ / ⎓ 20 °C (0,5 A UL)
Traduction à placer ici 5 mA/ °C
Maximum admissible current 20 A ≤ 10 ms
Minimum breaking current 10 mA
Leakage current < 5 mA
Voltage breaking capacity 250 V∿ / ⎓
Maximum voltage drop at terminals 3 wire 4V 2 wire 8V
Electrical life (operations) 108
Breakdown voltage acc. to IEC/EN 60664-1, IEC/EN 60255-5 2.5 kV to 1 mA / 1 min
Input type Volt-free contact 3-wire PNP output control option residual voltage : 0.4V whatever the timer power supply

Technical sketches

Solid state output

Solid state output

Function A

Function A
Delay on energisation 1 relay

Function Ac

Function Ac
Timing after closing and opening of control contact 1 relay

Function At

Function At
Timing on energisation with memory 1 relay

Function B

Function B
Timing on impulse one shot 1 relay

Function Bw

Function Bw
Pulse output (adjustable) 1 relay

Function C

Function C
Timing after impulse 1 relay

Function D

Function D
Flip-flop Pause start 1 relay

Function Di

Function Di
Flip-flop Pulse start 1 relay

Function H

Function H
Timing on energisation 1 relay

Function Ht

Function Ht
Delay on energisation with memory 1 relay
Copie de (Anglais) PH 8882600