KNA3-YS

KEY FEATURES

  • "Emergency stop" & "Gate monitoring" functions
  • Single channel operation
  • Security with redundancy and feedback circuit
  • 3 "NO" security contacts
  • 1 "NC" monitoring contact
  • Security category 3 (according to EN 954-1)
  • Performance Level (PL) d, safety category 3 to EN ISO 13849-1
  • SIL Claimed Level (SIL CL) 2 to IEC/EN 62061
  • Terminals : fixed screw terminals or plugin cage clamp terminals
TerminalsVoltagesSupply frequency range (Hz)OutputsCode
Screws24 V⎓No3 NO + 1 NC85102031
Screws110 V∿50/603 NO + 1 NC85102034
Screws230 V∿50/603 NO + 1 NC85102035

Specifications


Functions Emergency stop Monitoring of safety gates
Operation 1 channel
Control input Manual restart with On-button (Y1 - Y2 terminals) Automatic restart (Y1 - Y2 linked)
Failure detection Between terminal Y1 and common
Display of output state by LED Power supply : PWR Outputs : OUT (relays K1 & K2)
Supply voltage 85 102 031 / 85 103 031 : 24 V⎓ 85 102 034 / 85 103 034 : 110 V∿ 85 102 035 / 85 103 035 : 230 V∿
Supply frequency range (Hz) 50 / 60 for AC versions
Operating range ∿ : -15 % / +10 % U ⎓ : ± 10 % U (at 10 % residual ripple) ⎓ : - 15 % / +10 % U (at 48 % residual ripple)
Consumption 1,5 W (24 V⎓) 3,5 VA (230 V∿)
Initialization time 0,5 s
Maximum reset time 40 ms (24 V⎓) 200 ms (230 V∿)
Maximum response time on emergency stop 70 ms (24 V⎓) 35 ms (230 V∿)
Type Forcibly guided relays (positively driven)
Number of safety circuits 3 NO
Number of data circuits 1 NF
Nominal output voltage 250 V∿ max.
Max. thermal current I for each contact 5 A
Maximum power rating According to AC15 (NO contacts)  : 3 A / 230 V ∿ According to AC15 (NC contacts)  : 2 A / 230 V∿ According to DC13 (NO contacts)  : 4 A / 24 V⎓ ; 0,5 A / 110 V⎓ According to DC13 (NC contacts)  : 4 A / 24 V⎓
Electrical endurance At 5 A, 230 V∿, cos φ = 1 : 1,5 x 105 switching cycles At 8 A, 24 V⎓, according to DC 13 (NO contacts)  : 25 x 103 (ON : 0,4 s ; OFF : 9,6 s)
Mechanical life 20 x 106 switching cycles
Maximum rate 600 switching cycles / h
Protection against short circuits Max. fuse rating : 10 A gL Line circuit breaker : B 6 A

Operating temperature (o C) -15 →+55 °C
Storage temperature (0C) -25 →+85 °C
Altitude < 2000m
Climate resistance according to IEC/EN 60068-1 15 / 055 / 04

Vibration resistance according to IEC/EN 60068-2-6 Amplitude : 0,35 mm Frequency : 10 →55 Hz

Immunity to electrostatic discharges acc. IEC/EN 61000-4-2 8 kV (air)
Immunity to radiated, radio-frequency, electromagnetic field acc. IEC/EN 61000-4-3 10 V / m
Immunity to rapid transient bursts acc. to IEC/EN 61000-4-4 2 kV
Immunity to shock waves according to IEC/EN 61000-4-5 Between wires for power supply : 1 kV Between wires and ground : 2 kV
Immunity to radio frequency in common mode acc. to IEC/EN 61000-4-6 10 V
Interference suppression according to IEC/EN 55011 Limit value class B

Material : self-extinguishing (UL94VO) Thermoplastic with V0 extinction behaviour
Protection (IEC/EN 60529) - Casing IP40
Protection (IEC/EN 60529) - Term. block IP20
Mounting DIN-rail
Weight (g) 200 (24 V⎓) 270 (230 V∿)

Approvals CE, TÜV, cULus
Environmental directive 2002/95/CE RoHS
Environmental regulation 1907/2006 Reach
Security data according to EN ISO 13849-1 Performance Level (PL)  : d Category : 3
SIL Claimed Level (SIL CL) to IEC/EN 62061 2
Safety Integrity Level (SIL) according to CEI/EN 61508 2
Safety category to EN 954-1 3

Technical sketches

Safety related data

Safety related data

KNA3-YS - Screw terminals

KNA3-YS - Screw terminals

Front face drawing KNA3-YS

Front face drawing KNA3-YS

Contacts

Contacts
A1 (+)   : + / L A2  : - / N Y1, Y2  : Validation Input Y21 (-)   : Measure Output (-) of secondary used for example in IT networks for insulation control 13, 14, 23, 24, 33, 34  : Safety circuit outputs (forcibly guided NO contacts) 41, 42  : Monitoring output (forcibly guided NC contact)

Function diagram

Function diagram
PH 85102031

Single channel emergency-stop circuit without feed back loop, with or without automatic restart

Single channel emergency-stop circuit without feed back loop, with or without automatic restart
For automatic restart, terminals Y1 - Y2 must be linked. No ON-pushbutton necessary

Contact reinforcement by external contactors

Contact reinforcement by external contactors
For currents > 5 A, the output contacts can be reinforced by external contactors. Functioning of the external contactors is monitored by looping the NC contacts into the start circuit (Y1-Y2)