EUL

KEY FEATURES

  • Voltage monitoring
  • Measurement EUL : 0.2V to 60V
  • Measurement EUH : 15V to 600V
  • Automatic recognition AC/DC
  • Frequency up to 500 Hz
Measurement rangeSupply voltageCode
0,2 →60 V24 V ⎓84872020
0,2 →60 V24 V ∿84872021
0,2 →60 V120 V ∿84872023
0,2 →60 V230 V ∿84872024

Specifications


Supply voltage Un 24 V⎓, 120 V∿, 230 V∿
Polarity with ⎓ voltage DC : yes
Galvanic isolation of power supply/measurement DC : no galvanic isolation. In this case, the product power supply and measuring circuit power supply must be electrically isolated AC : galvanic isolation by transformer
Power consumption at Un DC : 1 W AC : 3 VA

Measurement range 0,2 →60 V E1-M : 0,2 →2 V E2-M : 1 →10 V E3-M : 6 →60 V
Input resistance E1-M : 2kΩ E2-M : 10kΩ E3-M : 60kΩ
Permanent overload at 20 °C E1-M : 4 V E2-M : 20 V E3-M : 120 V
Peak overload < 1ms at 20 oC E1-M : 50 V E2-M : 100 V E3-M : 300 V

Voltage supply tolerance -15 % / +15 % limited to -15 % / +10 % if products are mounted without space between them
Operating range 0,85 →1,15 Un
Immunity from micro power cuts 10 ms

Frequency of measured signal 40 →500 Hz
Threshold adjustment 10 →100 % of the measurement range
Hysteresis 5 →50 % of displayed threshold
Display precision ±10 % of full scale
Repetition accuracy with constant parameters ± 0,1 %
Measuring error with voltage drift < 0,5 %
Measuring error with temperature drift ± 0,05 % / °C

Delay on thresold crossing Tt 0,1 →3 s ±10 %

Type of output 1 changeover AgNi, 8 A∿ max
Type of contacts No cadmium
Maximum breaking voltage 250 V∿/⎓
Max. breaking current 8 A∿ max.
Min. breaking current 100 mA ∿/⎓
Electrical life (number of operations) AC 12 : 2000 VA - 105 AC 15 : Cos φ = 0,3 - 6 000 DC 13 : L/R = 300 ms - 6 000
Breaking capacity (resistive) 2000 VA∿
Maximum rate 360 operations/hour at full load
Operating categories acc. to IEC/EN 60947-5-1 AC12, AC15, DC13
Mechanical life (operations) 5 x 106

Insulation coordination (IEC/EN 60664-1) Overvoltage category III  : degree of pollution 2
Rated impulse withstand voltage (IEC/EN 60664-1) 4 kV (1,2 / 50 μs)
Dielectric strength (IEC/EN 60664-1) 2.5 kV AC 50 Hz 1 min.
Insulation resistance (IEC/EN 60664-1) > 100 MΩ / 500 V⎓

Display power supply Green LED
Display relay Yellow LED
Casing 22,5 mm
Mounting On 35 mm symmetrical DIN rail, IEC/EN 60715
Mounting position All positions
Protection (IEC/EN 60529) Terminal block : IP20 Casing : IP50
Weight 160 g
Connecting capacity IEC/EN 60947-1 Rigid  : 1 x 42 - 2 x 2.52 mm2 1 x 11 AWG - 2 x 14 AWG Flexible with ferrules  : 1 x 2.52 - 2 x 1.52 mm2 1 x 14 AWG - 2 x 16 AWG
Max. tightening torques IEC/EN 60947-1 0,6 mN / 5,3 Lbf.In
Operating temperature IEC/EN 60068-2 -20 →+60
Storage temperature IEC/EN 60068-2 -30 →+70
Humidity IEC/EN 60068-2-30 93 % RH max. without condensation
Vibrations according to IEC/EN60068-2-6 10 →55  Hz, A = 0.35 mm

Product standard IEC/EN 60255-1
Electromagnetic compatibility (EMC) IEC/EN 61000-6-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, IEC/EN 61000-6-4
Certifications UL, CSA
Marking CE (DBT) 2006/95/EC - EMC 2004/108/EC
Conformity with environmental directives RoHS

Technical sketches

Control of AC/DC voltage without memory

Control of AC/DC voltage without memory
Legend
1-
Treshold Ue
2-
Hysteresis
3-
UPPER function
4-
UNDER function
5-
Unit power-up
6-
Controlled voltage
When the value of the controlled voltage, AC or DC, reaches the treshold Ue displayed on the front face, the output relay changes state at the end of a time delay T1, which can be set on the front face at between 0.1 and 3s. Once the voltage drops below 5 to 50 % of the treshold (hysteresis), the output relay changes state again instantly. Changing the hysteresis onthe front face does not therefore modify the value of the preset treshold.

Control of AC/DC voltage with memory

Control of AC/DC voltage with memory
Legend
1-
Treshold Ue
2-
Hysteresis
3-
UPPER function
4-
UNDER function
5-
Unit power-up
6-
Controlled voltage
7-
Controlled voltage
When the value of the controlled voltage, AC or DC, reaches the treshold Ue displayed on the front face, the output relay changes state at the end of a time delay T1, which can be set on the front face at between 0.1 and 3s and remains latched in this position.

EUL / EUH

EUL / EUH

EUL

EUL
Legend
A1 - A2 : Supply voltage-

EUL / EUH

EUL / EUH
Legend
1-
Supply voltage to be monitored
PH 84872034