HNE

KEY FEATURES

  • Control of one or two levels
  • Filling or emptying function
  • HNM : Control by a resistive level probe
  • HNE : Control by a discrete sensor
SensingNominal voltage (V)Code
By discrete sensors24 →240 V ∿/⎓84870710

Specifications


Power consumption at Un 5 VA in ∿/2.7 W in ⎓
Immunity from micro power cuts 50 ms

Type of output 1 single pole changeover relay

Maximum reset time 1.7 s

Measurement range -
Low sensitivity adjustment (LS) -
Standard sensitivity adjustment St -
High sensitivity adjustment (HS) -
Adjustment of sensitivity -
Display precision ±10 % of full scale
Measuring error with temperature drift 0.5 % / °C in standardsensitivity
Measuring error with voltage drift 0 %/V across the whole range
Max. voltage at probe terminals 12 V
Max. current via probes 40 mA
Max. length of probe cables -
Max. capacity of probe cable (nF) 1 nF for HS range2.2 nF for St range4.7 nF for LS range
Input circuit 3-wire sensors

Weight 110 g

Supply voltage Un 24 V →240 V ∿/⎓
Voltage supply tolerance -15 % / +10 %
Operating range 20,4 →264 V ∿/⎓
Polarity with ⎓ voltage No
∿ supply voltage frequency 50/60 Hz ± 10 %
Galvanic isolation of power supply/measurement No

Timing Yelow DEL
Delay on thresold crossing 0,1 →5 s (0, + 10 %)
Repetition accuracy with constant parameters ± 2 %
Delay on pick-up 600 ms

Type of contacts No cadmium
Maximum breaking voltage 250 V ∿/⎓
Max. breaking current 5 A ∿/⎓
Min. breaking current 10 mA / 5 V ⎓
Electrical life (number of operations) 1 x 105
Breaking capacity (resistive) 1 250 VA ∿
Maximum rate 360 operations/hour at full load
Operating categories acc. to IEC/EN 60947-5-1 AC12, AC 13, AC 14, AC 15, DC 12, DC 13
Mechanical life (operations) 30 x 106

Nominal insulation voltage IEC/EN 60664-1 250 V
Insulation coordination (IEC/EN 60664-1) Overvoltage category III : degree of pollution 3
Rated impulse withstand voltage (IEC/EN 60664-1) 4 KV (1,2 / 50 μs)
Dielectric strength (IEC/EN 60664-1) 2 KV AC 50 Hz 1 min.
Insulation resistance (IEC/EN 60664-1) > 500 MΩ / 500 V ⎓

Display power supply Green LED
Display relay Yellow LED
Timing Yellow LED
Casing 35 mm
Mounting On 35 mm symmetrical DIN rail, IEC/EN 60715
Mounting position All positions
Material : enclosure plastic type VO to UL94 standard Incandescent wire test according to IEC 60695-2-11 & NF EN 60695-2-11
Protection (IEC/EN 60529) Terminal block : IP20 Casing : IP30
Connecting capacity IEC/EN 60947-1 Rigid : 1 x 42 - 2 x 2.52 mm2 1 x 11 AWG - 2 x 14 AWG Flexible with ferrules : 1 x 2.52 - 2 x 1.52 mm2 1 x 14 AWG - 2 x 16 AWG
Max. tightening torques IEC/EN 60947-1 0,6 →1 Nm / 5,3 →8,8 Lbf.In
Operating temperature IEC/EN 60068-2 -20 →+50 °C
Storage temperature IEC/EN 60068-2 -40 →+70 °C
Humidity IEC/EN 60068-2-30 2 x 24 hr cycle 95 % RH max. without condensation 55 °C
Vibrations according to IEC/EN60068-2-6 10 →150 Hz, A = 0.035 mm
Shocks IEC/EN 60068-2-6 5 g

Marking CE (DBT) 2006/95/EC - EMC 2004/108/EC
Product standard NF EN 60255-6 / IEC 60255-6 / UL 508 / CSA C22.2 N°14
Electromagnetic compatibility (EMC) Immunity EN 61000-6-2/IEC 61000-6-2 Emission EN 61000-6-4 2002/EN 61000-6-3 IEC 61000-6-4/IEC 61000-6-3 Emission EN 55022 class A
Certifications UL, CSA
Conformity with environmental directives RoHS

Technical sketches

HNE

HNE
HNM and HNE control relays are designed to monitor the levels of : - Conductive liquid (HNM) - Any other product (HNE) The HNM relay takes its measurements by means of resistive probes. The HNE relay takes its measurements by means of discrete sensors. Both these products actuate their output relay during emptying or filling of a tank. HNM relays control levels of conductive liquids. The principle is based on measuring the apparent resistance of the liquid between two submerged probes. When this value is below the preset threshold displayed on the front face of the unit, the relay changes state. To avoid electrolytic phenomena, an AC current runs across the probes. A rotary switch on the front face can be used to select the desired function and sensitivity range. A green LED indicates the presence of the supply voltage. A yellow LED indicates the status of the output relay. A yellow LED flashes during the time delay. A rotary switch on the front face can be used to select the sensitivity range, and the emptying or filling function. A second switch can be used to select the number of levels (1 or 2), as well as the type of time delay in the case of 1-level mode. The configuration of these switches is taken into account on energisation. If the switch is set to a non-conforming position on energisation, the product goes into fault mode, the output relay stays open and the LEDs flash to signal the position error. If the switch position changes while the unit is operating, all the LEDs flash but the product continues to work normally with the function selected on energisation prior to the change of position. The LEDs return to their normal state if the switch is reset to its initial position defined before the last energisation.

HNM-HNE - Emptying/filling function - two levels

HNM-HNE  - Emptying/filling function - two levels
Legend
1-
Maximum level
2-
Minimum level
3-
Output relay R filling function "Up"
4-
Output relay R emptying function "Down"
(Level : 2LS emptying function (Low sensitivity : 250Ω to 5 kΩ), St emptying (Standard sensitivity :   5 kΩ to 100 kΩ), HS emptying (High sensitivity :   50 kΩ to 1 MΩ). As long as the liquid level has not reached the probe maximum, the output relay stays open. Once the max. level is reached, the contact closes, thus allowing the tank to empty (valve opens, pump starts, etc). When the level drops below the min. level, the contact opens to interrupt the emptying process. NB : In two-level control mode the time delay for preventing wave effect is not active. (Level : 2, LS filling function (Low sensitivity : 250Ω to 5 kΩ), St filling (Standard sensitivity :   5 kΩ to 100 kΩ), HS filling (High sensitivity : 50 kΩ to 1 MΩ). As long as the liquid level has not reached the probe maximum, the output relay stays closed. Once the max. level is reached, the contact opens and pumping stops. When the level drops below the min. level, the contact closes again and pumping restarts so as to make the liquid level rise again. NB : In two-level control mode the time delay for preventing wave effect is not active.

HNM-HNE - One-level filling function/on-delay

HNM-HNE - One-level filling function/on-delay
Legend
1-
Min. probe level
2-
R output relay
(Level :   1LS filling function (Low sensitivity : 250Ω to 5 kΩ), St filling (Standard sensitivity :   5 kΩ to 100 kΩ), HS filling (High sensitivity : 50 kΩ to 1 MΩ). When the liquid level drops below the probe for a duration longer than the value of time delay Tt set on the front face, the relay closes and stays closed until the liquid level reaches the probe again. If the liquid level rises back above the level set before the end of the time delay, the relay does not close.

HNM-HNE - One-level filling function/off-delay

HNM-HNE - One-level filling function/off-delay
Legend
1-
Min. probe level
2-
R output relay
(Level : 1 - off-delay, LS filling function (Low sensitivity : 250Ω to 5 kΩ) or St filling (Standard sensitivity : 5 kΩ to 100 kΩ) or HS filling (High sensitivity : 50 kΩ to 1 MΩ). When the liquid level drops below the probe for a duration longer than the value of time delay Tt set on the front face, the relay closes instantly and stays closed until the liquid level reaches the probe again and stays above it for a duration longer than time delay Tt set on the front face. If the liquid level drops back below the level set before the end of the time delay, the relay stays closed.

HNM-HNE - One-level emptying function/on-delay

HNM-HNE - One-level emptying function/on-delay
Legend
1-
Min. probe level
2-
R output relay
(Level : 1 - on-delay, LS emptying function (Low sensitivity : 250Ω to 5 kWΩ), St emptying (Standard sensitivity :   5 kΩ to 100 kΩ), HS emptying (High sensitivity :   50 kΩ to 1 MΩ). When the liquid level rises above the probe for a duration longer than the value of time delay Tt set on the front face, the relay closes and stays closed until the liquid level drops back below the probe. If the liquid level drops back below the level set before the end of the time delay, the relay does not close.

HNM-HNE - One-level emptying function/off-delay

HNM-HNE - One-level emptying function/off-delay
Legend
1-
Min. probe level
2-
R output relay
(Level : 1 - off-delay, LS emptying function (Low sensitivity : 250Ω to 5 kΩ), St emptying (Standard sensitivity :   5 kΩ to 100 kΩ), HS emptying (High sensitivity :   50 kΩ to 1 MΩ). When the liquid level rises above the probe, the relay closes instantly and stays closed until the liquid level drops back below the probe for a duration longer than the value of time delay Tt set on the front face. If the liquid level rises back above the level set before the end of the time delay, the relay stays closed.

HNM-HNE

HNM-HNE

HNE

HNE
Legend
1-
1 A fast-blow fuse or cut-out