MWS

KEY FEATURES

  • Control of 3-phase networks : phase sequence, total phase failure
  • Multi-voltage from 3 x 208 to 3 x 480 V ∿
  • Controls its own supply voltage
  • True RMS measurement
  • LED status indication
FunctionNominal voltage (V)OutputCode
Phase sequence, phase failure3 x 208 →3 x 480 V ∿1 single pole changeover relay84873029

Specifications


Supply voltage Un 3 x 208 →3 x480 V ∿*
Voltage supply tolerance -12 % / +10 %
Operating range 183 →528 V ∿
Power consumption at Un 1,8 VA

Measurement ranges 183 →528 V ∿
Guaranteed phase failure detection threshold < 100 V∿
Voltage threshold hysteresis -
Display precision -
Maximum regeneration (phase failure) < 30 V∿

Alarm on delay time max. 130 ms
Delay on pick-up ≤ 650 ms

Type of output 1 single pole changeover relay
Maximum breaking voltage 250 V∿ / 8 A∿ - 250 V⎓ / 0,3 A
Max. breaking current 8 A∿ 250 V∿ - 8 A⎓ 30 V⎓
Min. breaking current 10 mA / 5 V⎓
Electrical life (number of operations) 1 x 105
Breaking capacity (V resistive) 2000 VA/80W
Mechanical life (operations) 10 x 106

Nominal insulation voltage IEC/EN 60664-1 400 V
Insulation resistance (IEC/EN 60664-1) > 500 MΩ / 500 V⎓

"Fault" indication -
Weight 80 g
Connecting capacity IEC/EN 60947-1 Rigid : 1 x 42 - 2 x 2,52 mm2 1 x 11 AWG - 2 x 14 AWG Flexible with ferrules : 1 x 2,52 - 2 x 1,52 mm2 1 x 14 AWG - 2 x 16 AWG
Max. tightening torques IEC/EN 60947-1 0,6 →1 Nm / 5,3 →8,8 Lbf.In
Vibrations according to IEC/EN60068-2-6 10 →150  Hz, A = 0,035 mm

*3 phase mains with earth

∿ supply voltage frequency 50 / 60 Hz ± 10 %
Galvanic isolation of power supply/measurement No
Immunity from micro power cuts 60 ms

Frequency of measured signal 50 →60 Hz ± 10 %

Type of contacts No cadmium
Max. breaking current EMWS - MWS2 : 5 A ∿/⎓ MWS : 8 A ∿ 250 V ∿ - 8 A ⎓ 30 V ⎓
Maximum rate 360 operations/hour at full load
Operating categories acc. to IEC/EN 60947-5-1 AC12, AC13, AC14, AC15, DC12, DC13

Insulation coordination (IEC/EN 60664-1) Overvoltage category III : degree of pollution 3
Rated impulse withstand voltage (IEC/EN 60664-1) 4 kV (1,2 / 50 μs)
Dielectric strength (IEC/EN 60664-1) 2 kV AC 50 Hz 1 min.

Display relay Yellow LED
Casing 17,5 mm
Mounting On 35 mm symmetrical DIN rail, IEC/EN 60715
Mounting position All positions
Material : enclosure plastic type VO to UL94 standard Incandescent wire test according to IEC/EN 60695-2-11
Protection (IEC/EN 60529) Terminal block : IP20 Casing : IP30
Operating temperature IEC/EN 60068-2 -20 →+50 °C
Storage temperature IEC/EN 60068-2 -40 →+70 °C
Humidity IEC/EN 60068-2-30 2 x 24 hr cycle 95 % RH max. without condensation 55 °C
Vibrations according to IEC/EN60068-2-6 10 →150 Hz, A = 0.035 mm
Shocks IEC/EN 60068-2-6 5 g

Product standard IEC/EN 50178
Electromagnetic compatibility (EMC) IEC/EN 61000-6-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, IEC/EN 61000-6-4
Certifications MWS, MWS2 : CE, UL, CSA EMWS : CE, UL (cULus)
Conformity with environmental directives RoHS

Technical sketches

MWS-MWS2 - Phase failure and sequence

MWS-MWS2 - Phase failure and sequence
Legend
1-
MWS : Relais R MWS2 : Relais R1/R2
2-
Temps de réponse à l'apparition d'un défaut (Tr)

MWS-MWS2

MWS-MWS2

MWS

MWS
Legend
1-
100 mA fast-blow fuse

MWS

MWS
PH RMC2 MWS

Share
Share
venenatis vel, commodo lectus elit. ut